This 7530 wall-mount CO2 Controller comes with an external CO2 sensing probe that will help in measuring CO2 levels in closed spaces. You can use it for CO2 monitoring in indoor air quality and greenhouse CO2 measurements. It can also be used and operated in other workspaces like offices, hospitals, schools, stations, residential, commercial buildings, or home usage. You can also use it in controlling another connected instrument such as a CO2 generator or ventilation fan easily by two modes (the plant OR human mode) to override the controlling in low or high CO2 concentration.
7530 offers you a simple and affordable way to control and monitor CO2 levels in a Greenhouse, residential, hydroponics, mushroom farm, commercial building, and so on.
(Buyer's Note: If you wish to buy CO2 tubing, kindly click here)
Features:
- Accurate 2-Channel low drift NDIR CO2 measurement
- With a 4.5M External CO2 sensor to be used in closed space
- Display real-time CO2 value
- Display CO2 chart with adjustable time scale (week/day/hour/min/auto)
- Auto Max. /Min. Recall on the CO2 chart
- Programmable CO2 zone value & CO2 center value to control output power on/off
- An audible alarm that warns CO2 concentration
- Target zone indicator on CO2 chart
- Built-in Day/Night auto-detection on CO2 probe to override CO2 control
- Backlight to assist the operation in a dark place
- Powered by AC100~240 VAC directly
- The sensing probe cable is 4.5 meters long to extend your measure spot 4.5 meters away from the display
- Installed with 3kA@300VAC fuse in meter to avoid damage by a power overload
Specifications:
- Measuring range: 0~5000 ppm
- Resolution: 1ppm (0-1000); 5ppm (1000-2000); 10ppm (>2000)
- Accuracy:
- CO2 below 3000ppm ±50ppm or ±5% of reading, whichever is greater
- CO2 above 3000ppm ±7% of reading
- Warm-up time: 30 seconds
- Response time CO2:
- <2min for 63% of step changes or
- <4.6min for 90% step change
- LCD size: 47 x 104 mm
- Meter size: 158 x 106 x 50 mm
- Sensor size: 124 x 33 x 26 mm
- Operating condition: 0~50°C , 5~95% RH (avoid condensation)
- Storage condition: -20~ 60°C, 5~95%RH (avoid condensation)
- Power supply: AC100~240VAC
- Piggyback socket load 5A@250VAC; 10A@120VAC
Set Includes:
- 1 x CO2 Meter (Controller + Sensor)
- Screws and tapes
- English Instruction Manual
- Standard factory packaging